Legionella – Installation Principles and Prevention Methods (Rørcenter-anvisning 017)
Rørcenter-anvisning 017, published in May 2019 by the Danish Technological Institute (Teknologisk Institut), serves as a technical guidance document for the prevention and control of Legionella in hot water installations. This second edition was developed for the Danish Transport, Construction and Housing Authority (Trafik- Bygge- og Boligstyrelsen). It operates within the legal framework of the Danish Building Act (Byggeloven) and the Building Regulations 2018 (BR18), providing specific implementation rules for health and safety compliance in domestic water systems.
The document governs the design, installation, operation, and maintenance of various hot water systems, including central heating in single-family homes, district heating, heat pumps, and solar thermal systems. It defines regulatory requirements found in DS 439 (Code of Practice for water installations), DS 469 (Heating and cooling systems), and DS 452 (Thermal insulation of technical installations). The scope includes technical strategies to eliminate biofilm, manage stagnation, and maintain temperature thresholds across complex pipe networks in residential and institutional buildings.
Professional guidance within this document covers risk assessment procedures, the roles of property owners, and technical methods for bacterial eradication. It details structural requirements for installations to ensure that the risk of microbial colonization is minimized through correct pipe sizing, insulation, and hydraulic balancing.
Legal Framework and Responsibilities
Under the Danish Building Act, specifically §§ 14 and 17, the owner of a property is legally responsible for ensuring that installations do not pose a danger to residents. Building Regulations BR18 mandate that water systems must be designed to avoid health risks from bacterial growth.
- BR18 § 404: Requires water installations to be dimensioned according to DS 439 to ensure adequate supply.
- BR18 § 405: Mandates that systems function without risk of Legionella growth.
- BR18 § 419: Requires a comprehensive operation and maintenance manual, including technical drawings and maintenance intervals.
- BR18 § 416: Restricts materials to those that do not promote microbial growth or release harmful substances.
Temperature Thresholds for Legionella Control
Temperature management is the primary method for controlling Legionella growth. The document establishes specific biological responses based on water temperature levels:
- Below 20 °C: Bacteria survive but typically remain in a dormant state.
- 20 °C to 50 °C: Active growth range, with the optimal level between 35 °C and 46 °C.
- Over 50 °C: Survival is possible, but no active growth occurs.
- 55 °C: Bacterial death occurs within 5 to 6 hours.
- 60 °C: Bacterial death occurs within 30 minutes.
- 66 °C: Bacterial death occurs within 2 minutes.
System Design and Installation Standards
To prevent colonization, systems must avoid dead ends (døde ender) and ensure constant circulation where required. DS 439 specifies that systems must be capable of raising temperatures to 60 °C if contamination is detected.
- Circulation: In larger systems, the return temperature should not drop below 50 °C.
- Insulation: Pipes must be insulated per DS 452 to prevent cold water from warming above 20 °C and hot water from cooling into the growth range.
- Tank Stratification: Hot water tanks should be designed to ensure layers of different temperatures do not mix in a way that creates a growth zone.
- Shower Hoses: Recommended replacement every 1-2 years to prevent biofilm accumulation.
Eradication Methods
When Legionella concentrations exceed acceptable limits, the document outlines several technical intervention methods:
- Thermal Disinfection: Also known as Temperature Gymnastics, involving flushing the system with water at 70 °C for at least 30 minutes.
- UV Radiation: Destroys bacterial DNA at the point of use but provides no residual effect against biofilm in the pipes.
- Chlorine Dioxide: A chemical disinfectant effective against biofilm with long-term residual activity.
- Hypochlorous Acid: Produced on-site via electrolysis of salt water to kill bacteria and remove biofilm.
- Copper-Silver Ionization: An electrochemical process that uses ions to disrupt bacterial cell walls, though its use in Denmark is currently restricted.
Frequently Asked Questions
What is the optimal temperature for Legionella growth?
The optimal growth temperature for Legionella bacteria is between 35 °C and 46 °C.
What are the temperature requirements for the furthest tap point?
According to the recommended drift temperatures, the water at the furthest tap must be at least 50 °C to prevent bacterial growth.
How often should hot water tanks be cleaned?
The interior surfaces and heating coils of hot water tanks should be cleaned and descaled annually.
What is the maximum allowed temperature for cold water?
Cold water should ideally be below 12 °C at the tap, and must not exceed 20 °C to avoid risk of bacterial growth.
What action is required if Legionella levels exceed 10,000 cfu/liter?
An immediate review of control measures is required, and disinfection of the entire system must be performed.
Who is responsible for Legionella risk assessment in a building?
Under the Building Act, the primary responsibility lies with the property owner to ensure the installation is safe for occupants.