Building Regulations Guidance (BR18) Annex 11a – Site Plans for Temporary Outdoor Events
This guidance, designated as Bilag 11a, was issued by the Danish Social- og Boligstyrelsen (Social and Housing Authority) on September 2, 2024, as part of the official guidance for Chapter 5 – Fire of the Danish Building Regulations. It specifically addresses the requirements for arrangementsplaner (site plans) for temporary outdoor events. The document operates within the framework of the Byggeloven (Building Act) and provides the technical basis for municipal authorities to evaluate fire safety and site layout for temporary installations.
The regulatory scope is limited to temporary outdoor events with a maximum duration of 6 weeks. It applies to gatherings of more than 150 persons that include elements such as forsamlingstelte (assembly tents), campingområder (camping areas), salgsområder (sales areas), and tivoliområder (carnival areas). The guidance details the mandatory documentation required by the kommunalbestyrelsen (municipal board), specifically focusing on physical distancing, evacuation safety, and access for emergency services. It distinguishes between general site planning and the detailed internal layout of specific zones, which are covered in Bilag 11.
This technical reference provides architects, event planners, and safety professionals with specific measurement thresholds, including mandatory distances to property boundaries and technical specifications for fire access roads, ensuring that temporary event sites meet national safety standards before operations commence.
Authority Processing and Site Documentation
Documentation for temporary events exceeding 150 persons must be submitted to the municipality at least 4 weeks before the area is taken into use. This submission must include a site plan that provides a representative overview of the entire event area.
- Mandatory Elements: The site plan must include assembly tents, circus tents, camping areas, sales areas, parking, stages, and existing buildings.
- Spatial Definition: Event organizers must define the area boundaries. While physical fencing is not required, the spatial extent must be known to all staff to ensure operational compliance.
- Repeated Events: Existing site plans may be reused for recurring events, provided there are no changes to the placement or use of individual elements.
Distancing Requirements and Boundary Safety
To prevent the spread of fire between the event site and neighboring properties, specific minimum distances to the naboskel (property boundary) are established for different structures.
- 5.0 Meters: Minimum distance for assembly tents, sales areas, and camping areas to the property boundary.
- 2.5 Meters: Distance for buildings with K1 10 / B-s1,d0 (Class 1) cladding, such as masonry or concrete.
- 5.0 Meters: Distance for buildings with K1 10 / D-s2,d2 (Class 2) cladding, such as wooden facades.
- 10.0 Meters: Distance for buildings with non-fire-protected thatched roofs.
Where multiple structures are placed on the same or adjacent plots, the internal distance must equal the sum of their individual boundary distance requirements. For example, a tent (5.0m) next to a Class 1 building (2.5m) requires a total separation of 7.5 meters.
Evacuation and Emergency Access
The site must be designed to ensure all persons can move quickly to a sikkert sted (safe place) unaffected by potential incidents. This safe place can be located outside the event area or within prepared evacuation zones.
- Brandveje (Fire Roads): Access roads must be at least 3.0 meters wide and have a clear height of 3.4 meters.
- Unloading Areas: At locations where personnel must exit vehicles to deploy equipment, the road width must increase to at least 5.0 meters.
- Hose Reach: Fire roads must be laid out so that the maximum walking distance from a vehicle exit point to any point on the site is 80 meters.
- Load Bearing: All fire roads must be capable of supporting heavy emergency vehicles.
Frequently Asked Questions
What is the maximum duration for a temporary event under this guidance?
A temporary outdoor event covered by this annex must have a duration of no more than 6 weeks.
When is a site plan mandatory for outdoor events?
A site plan must be submitted for events exceeding 150 persons that include assembly tents, camping areas, or sales areas.
What is the deadline for submitting the site plan to the municipality?
The documentation must be submitted to the municipal authority at least 4 weeks before the event or camping area is taken into use.
What is the minimum road width for fire department access?
Fire access roads must have a minimum width of 3.0 meters and a minimum free height of 3.4 meters.
How far must an assembly tent be placed from the property boundary?
Assembly tents must maintain a minimum distance of 5.0 meters from the property boundary (naboskel).
What is the maximum hose reach distance allowed on the site?
Fire roads must be positioned so that the walking distance (ganglængde) from the emergency vehicle to any point is at most 80 meters.