Annex 15 – Pre-accepted Fire Safety Solutions for Secondary Buildings Near Commercial and Multi-Unit Properties
Annex 15 is a supplement to the Danish Building Regulations 2018 (BR18) guideline for Chapter 5 - Fire. Issued by the Bolig- og Planstyrelsen (Danish Authority of Social Services and Housing), this document establishes the pre-accepted technical solutions for fire safety in secondary structures located on the same plots as non-residential buildings or multi-story housing. It serves as the primary compliance framework for documenting that secondary constructions meet the statutory fire safety requirements of the Danish building code.
The scope of the document is limited to secondary buildings categorized under Use Category 1 and Risk Class 1, which are constructed as a single story above ground. Regulated structures include carports, garages, storage sheds, waste management rooms, and simple weather protection for technical installations or bicycle parking. The regulations define specific area thresholds, such as a maximum of 150 m² for standard secondary buildings and up to 600 m² for open structures like carports, provided they meet specific height and ventilation criteria. The annex explicitly excludes buildings intended for overnight stays, kitchens, or changing facilities.
The document provides structured guidance on evacuation routes, structural fire resistance, and the prevention of fire spread across property lines or between adjacent buildings. It details technical requirements for materials, distances to primary buildings, and the necessary documentation for Fire Class 1 projects.
Scope and Building Classification
The annex applies to new secondary buildings associated with multi-story housing, commercial properties, hotels, and educational or daycare institutions. It does not apply to integrated structures sharing a roof with the primary building.
- Secondary Buildings: Max 150 m² area for closed structures.
- Open Structures: Max 600 m² for structures open on at least two sides, provided the distance to an open side does not exceed 8.0 m and height is under 2.5 m.
- Exclusions: Facilities for sleeping, eating, or bathing; nurseries in daycare centers; closed conservatories; and commercial warehouses are not covered.
Evacuation and Rescue
In accordance with BR18 § 91, all rooms in secondary buildings must be designed to facilitate safe escape and rescue by emergency services.
- Direct Access: Every room must have at least one exit leading directly to the terrain outside.
- Large Rooms: Rooms exceeding 50 m² require at least two exits. One must lead to the outside, while the second can lead to an open covered area with a maximum travel distance of 8.0 m.
Structural Fire Resistance
Load-bearing elements must maintain stability to ensure safe evacuation and allow emergency services to operate. Requirements vary based on the total area of the structure.
- Area ≤ 50 m²: No specific requirements for the fire resistance of load-bearing structures.
- Area > 50 m²: Load-bearing elements must meet Class R 15 standards. This requirement is waived if the building uses a light roof classified as E-d2.
Distances and Fire Spread Prevention
Placement of secondary buildings must prevent fire spread to other buildings on the same plot and to neighboring properties. Distances are measured horizontally regardless of terrain differences.
- Neighboring Boundaries: Open structures ≤ 50 m² using A2-s1,d0 materials can be placed at the boundary. Closed structures ≤ 50 m² must maintain a 2.5 m distance.
- Primary Buildings: Secondary structures over 50 m² must maintain at least 5.0 m distance from primary buildings unless fire separation walls are installed.
- Fire Separation: Structures placed closer than specified must be separated by walls rated EI 60 or EI 120 depending on the use category of the primary building.
Frequently Asked Questions
What is the maximum size for a secondary building under these rules?
The maximum area is 150 m² for standard structures, while open structures like carports can be up to 600 m² if they are open on two sides and under 2.5 m tall.
Can a secondary building be used for overnight stays?
No, Annex 15 specifically states that secondary buildings covered by these solutions must not be used for overnight accommodation, dining, or as changing rooms.
What are the fire resistance requirements for load-bearing structures?
Structures larger than 50 m² must generally meet Class R 15, unless they have a light roof classified as E-d2. There are no requirements for structures 50 m² or smaller.
How many exits are required for a large storage shed?
Any room in a secondary building exceeding 50 m² must have at least two exits, one of which must lead directly to the outside terrain.
What distance must be kept from the neighbor's boundary?
For closed secondary buildings up to 50 m², the minimum distance is 2.5 m. Open structures using non-combustible materials can be placed at the boundary if one side is at least 1.0 m from the fence.
Are thatched roofs allowed on secondary buildings?
Yes, thatched roofs are permitted. If fire-protected, they must maintain a 5.0 m distance from boundaries; if not fire-protected, the distance increases to 10.0 m.