DA DB-SUA / 2 – Accessibility in Existing Buildings Compliance Document
The DA DB-SUA / 2 is a technical support document issued by the Ministerio de Fomento through the Dirección General de Arquitectura, Vivienda y Suelo in Spain. This document, titled Adecuación efectiva de las condiciones de accesibilidad en edificios existentes, provides specific criteria for the flexible application of accessibility regulations within the framework of the Código Técnico de la Edificación (CTE). It primarily serves as a guide for adapting buildings and establishments whose building license applications were submitted prior to September 12, 2010.
The regulatory scope encompasses structural and functional requirements for accessibility and non-discrimination of persons with disabilities. The document details basic conditions and admissible tolerances for elements such as itinerarios accesibles (accessible routes), slopes, stairways, and ramps. It references legal frameworks including Real Decreto Legislativo 7/2015 and technical standards like the DB SUA (Security of utilization and accessibility) and DB SI (Fire safety).
The following sections detail the flexibility criteria and technical specifications for mechanical devices, elevator installations, and accessible toilet facilities as defined in the June 2018 edition of the document.
Application Criteria and Flexibility
The document establishes criteria for when full compliance with DB SUA and DB SI is not urbanistically, technically, or economically viable. In such cases, the designer may apply alternative measures that facilitate access to the highest degree possible. Admissible tolerances are defined in specific tables to determine if an existing state is acceptable even if it does not strictly meet standard code requirements.
- Existing Buildings: Defined as those with license applications prior to September 12, 2010.
- Admissible Tolerances: Limits within which existing conditions are considered valid during interventions.
- Compensatory Measures: Actions required when structural elements cannot be modified to reduce associated risks.
Tolerances for Ramps and Stairs
For existing buildings, the document permits specific deviations from standard dimensions for itinerarios accesibles. These tolerances apply to slopes, widths, and the configuration of landings and handrails.
- Ramp Slopes: Maximum of 12% for sections up to 3 m, 10% up to 10 m, and 8% up to 15 m.
- Stair Risers: Variations of ± 1 cm between risers in public use stairs are permitted if risk-reduction measures are implemented.
- Width: A minimum clear width of 0.90 m is allowed in straight sections between handrails for existing ramps.
- Landings: Intermediate landings and changes of direction must have a minimum depth of 1.20 m.
Mechanical Elevation Devices
Annex A defines the conditions for installing vertical and inclined lift platforms (salvaescaleras) when the installation of a standard elevator or ramp is unviable. These devices are intended to save small level changes, typically not exceeding one floor.
- Vertical Platforms: Must comply with Directive 2006/42/CE and UNE-EN 81-41. Minimum platform dimensions vary based on door configuration, such as 125 x 125 cm for adjacent doors.
- Inclined Platforms: Must follow UNE-EN 81-40. They are considered a secondary option when vertical platforms are not feasible and must not interfere with emergency evacuation routes.
- Load Requirements: Minimum calculation load of 250 kg/m² is generally required.
Elevator Installation in Residential Buildings
Annex B focuses on the incorporation of elevators in existing collective housing. It prioritizes interventions that satisfy accessibility while considering the impact on third parties and building safety.
- Cabin Dimensions: Minimum dimensions of 100 x 125 cm for a load of 450 kg for Type A manual or motorized wheelchairs.
- Intervention Types: Installation in interior common areas, interior patios, on the facade, or through private areas.
- Structural Impact: The solution must ensure no incompatible load increase on the existing structure according to DB SE.
Frequently Asked Questions
Which buildings fall under the scope of DA DB-SUA / 2?
Buildings and establishments whose construction license was requested before September 12, 2010, are eligible for the flexibility criteria defined in this document.
What is the maximum permitted slope for an existing ramp under tolerance rules?
For ramps up to 3 meters in length, a maximum slope of 12% is admissible. For lengths up to 10 meters, the limit is 10%.
Are inclined lift platforms (salvaescaleras) considered a primary accessibility solution?
No, they are considered a second alternative option to be used only when ramps or vertical lift platforms are justified as technically or economically unviable.
What is the minimum door width for an elevator to be considered accessible?
According to the document and referenced standards UNE-EN 81-70 and 81-82, the minimum clear passage width for an elevator door is 80 cm.
Can the width of an evacuation staircase be reduced to install an elevator?
Yes, reductions are permitted down to 0.80 m for downward evacuation and specific calculated widths for upward evacuation, provided no other alternatives exist.
What are the minimum dimensions for an accessible toilet in a small premises?
In premises with public use areas under 100 m² and occupancy under 50 people, shared toilets or a maneuvering space reduced to 1.20 m in diameter may be permitted.