Documento Básico HE Ahorro de energía – Spanish Energy Saving Building Code
The Documento Básico HE Ahorro de energía (DB-HE) is a regulatory statute issued by the Ministerio de Transportes, Movilidad y Agenda Urbana of Spain. It constitutes a fundamental part of the Código Técnico de la Edificación (CTE), establishing the mandatory rules and procedures to satisfy the basic requirement of energy savings in buildings. This consolidated version includes the modifications introduced by Real Decreto 450/2022, ensuring the legal framework aligns with contemporary efficiency standards for both new constructions and interventions in existing buildings.
The document's scope covers the limitation of energy consumption, control of thermal demand, efficiency of thermal and lighting installations, and the mandatory integration of renewable energy sources. It is structured into seven primary sections: HE 0 (Limitation of energy consumption), HE 1 (Conditions for energy demand control), HE 2 (Thermal installations), HE 3 (Lighting installations), HE 4 (Renewable energy for domestic hot water), HE 5 (Renewable electricity generation), and HE 6 (Electric vehicle charging infrastructure). Additionally, it defines technical parameters such as consumo de energía primaria no renovable and transmitancia térmica.
Technical professionals must apply these standards to ensure buildings reach the status of a consumo de energía casi nulo (nearly zero-energy building). The following sections detail the specific thresholds, calculation procedures, and compliance criteria defined within the official text.
HE 0: Limitation of Energy Consumption
This section limits building energy use based on the winter climate zone, building use, and the scope of intervention. It establishes limits for both non-renewable primary energy consumption (Cep,nren) and total primary energy consumption (Cep,tot).
- New private residential buildings: Limits range from 20 to 43 kW·h/m²·year for non-renewable energy depending on the climate zone (A to E).
- Total primary energy limit: For new residential buildings, values range from 40 to 86 kW·h/m²·year.
- Extra-peninsular territories: Values for Baleares, Canarias, Ceuta, and Melilla are subject to specific multipliers (e.g., 1.25 for non-renewable energy in residential use).
HE 1: Control of Energy Demand
Section HE 1 regulates the thermal envelope to limit energy needs for thermal comfort. It defines maximum values for thermal transmittance (U) and air permeability.
- Thermal Transmittance (U): Limits are set for walls, floors, roofs, and openings (windows/doors) according to climate zones.
- Solar Control (qsol;jul): New residential buildings must not exceed a solar control parameter of 2.00 kWh/m²·month in July.
- Air Permeability: New residential buildings with a useful area over 120 m² must maintain an air change rate (n50) not exceeding 6 h⁻¹ for low compactness or 3 h⁻¹ for high compactness.
HE 4 & HE 5: Renewable Energy Integration
These sections mandate a minimum contribution from renewable sources for domestic hot water (ACS) and electricity generation.
- ACS Renewable Contribution: At least 70% of the annual energy demand for ACS and indoor pool heating must be covered by renewable sources.
- Threshold for HE 4: Applicable to new buildings with an ACS demand exceeding 100 l/d.
- Electricity Generation (HE 5): Mandatory for non-residential buildings over 1,000 m² of constructed area, requiring a minimum installed power based on the building's footprint and roof area.
HE 6: Electric Vehicle Charging Infrastructure
Section HE 6 establishes minimum requirements for charging stations and cable management systems in parking areas.
- Private Residential: Mandatory installation of cable ducting for 100% of parking spaces to allow for future charging station supply.
- Non-Residential: Requires ducting for at least 20% of spaces and one charging station for every 40 spaces or fraction thereof.
- Public Administration: Buildings owned by the General State Administration must install one charging station for every 20 parking spaces.
Frequently Asked Questions
What is the minimum renewable energy contribution for domestic hot water (ACS)?
According to section HE 4, at least 70% of the annual energy demand for ACS must be covered by renewable sources or renewable cogeneration processes.
Does DB-HE apply to protected historical buildings?
Officially protected buildings may be excluded if compliance would unacceptably alter their character or appearance, as determined by the relevant heritage authority.
What is a 'nearly zero-energy building' (nZEB) according to Spanish regulations?
An nZEB is defined as a building, new or existing, that meets the regulatory requirements established in DB-HE regarding the limitation of energy consumption for new constructions.
When is electricity generation from renewable sources mandatory?
Under HE 5, it is mandatory for new or renovated non-residential buildings with a constructed area exceeding 1,000 m².
What are the air permeability limits for new residential buildings?
For buildings over 120 m², the n50 value must not exceed 6 h⁻¹ if the V/A ratio is ≤ 2, or 3 h⁻¹ if the V/A ratio is ≥ 4.
How are climate zones determined in Spain for energy compliance?
Climate zones are determined based on the province and the altitude of the site above sea level, as detailed in the tables of Anejo B.