Bilag 5: Præ-accepterede løsninger for undervisningslokaler – Fire Safety in Danish Educational Facilities
This document, known as Bilag 5, is a technical annex to the guidance for Chapter 5 (Fire) of the Danish Building Regulations 2018 (BR18). Published by the Bolig- og Planstyrelsen (Danish Authority for Social Services and Housing), this version 1.1 (11-01-2022) provides pre-accepted technical solutions for fire safety in educational premises. It sits within the wider legal framework of BR18 § 2, governing new constructions, extensions, and changes in the use of existing buildings.
The scope of the guidance is limited to building sections containing educational rooms, school-based after-care facilities (skolefritidsordninger), and associated support functions like meeting rooms, offices, and toilets. It specifically regulates building sections categorised under Usage Category 2 (anvendelseskategori 2) and Risk Classes 1-3 (risikoklasse 1-3). Key technical domains include evacuation strategy, rescue openings (redningsåbninger), fire cells (brandceller), fire sections (brandsektioner), and specific requirements for fire spread through materials and installations. The annex identifies concrete thresholds, such as the limit of 50 persons per fire cell, and defines the structural requirements for load-bearing elements and surface finishes.
The structured sections below detail the specific pre-accepted solutions for evacuation, technical installations, and fire protection of building components as defined in the official guidance.
Evacuation and Person Rescue
Design and execution of escape routes must allow for rapid and safe evacuation to terrain level or a secure location within the building. For educational facilities, the following functional requirements apply to escape routes and rescue openings:
- Max Distance: The walking distance within a fire cell to an exit must not exceed 30 metres.
- Exit Quantity: Rooms intended for more than 50 persons or rooms with high fire risk (e.g., school kitchens, laboratories) must have at least two exits.
- Rescue Openings: A fire cell must have at least one rescue opening per 10 persons. For example, a room for 28 persons requires 3 rescue openings.
- Opening Dimensions: Rescue openings must have a combined height and width of at least 1.5 metres, with a minimum height of 0.6 metres and a minimum width of 0.5 metres.
Fire Spread and Material Classes
External and internal surfaces are regulated to prevent the development of heat, smoke, and burning droplets. Specific material classes and distances to boundaries are established to limit fire spread between buildings.
- External Walls: Standard cladding must meet class K1 10 / B-s1,d0 (Class 1 cladding).
- Boundary Distances: Buildings must generally be placed at least 2.5 metres from the property boundary, road centre, or path centre.
- Insulation: External insulation must be interrupted by fire-separating walls and floor divisions. Insulation materials must typically be class A2-s1,d0 (non-combustible) or B-s1,d0 (Class A material) depending on building height.
- Roof Coverings: Must meet class BROOF(t2) (Class T roof covering).
Structural and Fire Separation Requirements
Building sections are divided into fire-technical units to ensure stability during evacuation and to facilitate rescue services.
- Fire Sections: Boundaries for fire sections must have a fire resistance of at least EI 60 or EI 60 / A2-s1,d0 depending on the floor height over terrain.
- Fire Cells: Rooms such as classrooms, kitchens, and laboratories must be designed as independent fire cells with boundaries of at least EI 60.
- Floor Height Thresholds: For buildings with a top floor height exceeding 12.0 metres over terrain, enhanced fire resistance requirements for load-bearing structures apply.
- Fire Doors: Doors in fire section walls must be at least class EI2 60-C (BD-door 60).
Frequently Asked Questions
What is the maximum person capacity per fire cell in this annex?
The pre-accepted solutions in Bilag 5 apply to educational rooms and fire cells designed for a maximum of 50 persons.
What are the required dimensions for a rescue opening?
The sum of the clear height and clear width must be at least 1.5 metres, with the height being at least 0.6 metres and the width at least 0.5 metres.
When is an automatic fire warning system required?
For building sections in risk classes 1-3 with escape routes, a warning system is required if the section is intended for more than 150 persons.
What is the maximum walking distance to an exit in an escape route corridor?
The distance between escape route stairs in a corridor must not exceed 60 metres, and the distance from a fire cell door to the nearest stair must not exceed 30 metres.
What is the required ceiling height in escape routes?
Escape routes, including corridors and stairs, must have a clear ceiling height of at least 2.1 metres.
Are specific door opening directions required for schools?
Doors in escape routes serving more than 150 persons must open in the direction of escape.
Can fire cells have only one exit?
A fire cell under 150 m² for max 50 persons can have one exit if it also has rescue openings and the walking distance requirements are met.
What fire class is required for a fire-separating wall?
Fire section walls must generally have a fire resistance of at least EI 60 (BS-bygningsdel 60).