Bygningsreglementets vejledning til kapitel 5 - Brand: General Fire Safety Guidelines
The Bygningsreglementets vejledning til kapitel 5 - Brand (Version 3.0, May 10, 2022) is the official guidance document issued by the Danish Bolig- og Planstyrelsen. It details the administrative and technical framework for fire safety compliance under the Danish Building Regulations 2018 (BR18). The document serves as the primary reference for demonstrating that a building meets the functional safety requirements specified in BR18 §§ 506–522 and technical requirements in §§ 82–158.
The scope of the guidance covers the identification and categorization of building sections into Use Categories (anvendelseskategorier), Risk Classes (risikoklasser), and Fire Classes (brandklasser). It defines five distinct methods for documenting fire safety, ranging from following præ-accepterede løsninger (pre-accepted solutions) to advanced brandteknisk dimensionering (fire safety engineering). The document also outlines the requirements for Certified Fire Consultants (certificeret brandrådgiver) and the testing and classification standards for building materials and technical installations.
This document provides the structured methodology necessary for fire safety strategies, permit applications, and the final documentation required before a building can be occupied. It establishes the relationship between building complexity and the required level of professional documentation.
Methods for Fire Safety Documentation
Building owners must document that the required safety level is achieved through one or a combination of the following five methods specified in BR18 § 492:
- Pre-accepted solutions: Application of solutions described in the annexes of the guidance in their full extent.
- Fire safety justified assessment (BBV): Used for simple deviations from pre-accepted solutions where the safety level remains equal.
- Comparative analysis: Evaluating a chosen solution against a reference building or general solution.
- Fire safety engineering: Calculation-based verification of evacuation safety and fire spread prevention.
- Fire testing: Documentation through physical experiments representing specific building components.
Use Categories (Anvendelseskategorier)
Every building section must be assigned to one of six Use Categories based on four criteria: sleeping accommodations, familiarity with escape routes, the ability of occupants to self-rescue, and the maximum number of people.
- Category 1: Offices, industrial buildings, and garages where occupants know the escape routes and can self-rescue.
- Category 2: Classrooms and day centers for up to 50 people who do not know the escape routes but can self-rescue.
- Category 3: Shops, cinemas, and restaurants for more than 50 people who do not know the escape routes but can self-rescue.
- Category 4: Residential units including houses and apartments with sleeping accommodations for occupants who know the escape routes.
- Category 5: Hotels and hostels with sleeping accommodations for occupants who do not know the escape routes.
- Category 6: Hospitals, nursing homes, and prisons for occupants who cannot self-rescue.
Risk Classes and Fire Classes
The Risk Class (1–4) is determined by the use category, fire load, and building height. This classification dictates the Fire Class (1–4) which determines the documentation complexity and professional qualifications required.
- Fire Class 1: Simple, traditional buildings (e.g., houses < 600 m²) where pre-accepted solutions are used; no certified fire consultant is required.
- Fire Class 2: Buildings in Risk Class 1-3 following pre-accepted solutions with limited deviations; requires a certified fire consultant.
- Fire Class 3 & 4: Complex or non-traditional buildings using engineering methods or comparative analyses; requires a high-level certified fire consultant and potentially third-party control.
Deviations in Fire Class 2
Buildings may remain in Fire Class 2 despite minor deviations from pre-accepted solutions if specific conditions are met:
- A maximum of three concrete deviations are permitted per building section.
- Measurable deviations (e.g., escape route length, door width) must not exceed 10% of the prescribed value.
- Deviations are not permitted for material classification, fire resistance of load-bearing structures, or technical installations.
Frequently Asked Questions
When is a certified fire consultant required in Denmark?
A certified fire consultant is mandatory for all building permit applications in Fire Class 2, 3, and 4. Buildings in Fire Class 1 are exempt from this requirement.
What defines a building as Fire Class 1?
It must be a simple, traditional building in Risk Class 1, such as a single-family house with a maximum area of 600 m² and no more than one floor below ground or three floors above ground.
What is the maximum person limit for Use Category 2?
Use Category 2 is typically for sections designed for up to 50 people, such as small shops or smaller educational rooms.
Can fire testing be used to document an entire building?
No, fire testing usually documents specific technical solutions or components and serves as a supplement to other documentation methods.
What are the documentation requirements for building materials?
Materials must be documented through CE-marking, fire testing according to European standards, Eurocode calculations, or commission-delegated regulations.
How is a building height measured for Risk Class 1?
For Risk Class 1, buildings typically have a maximum floor height of 5.0 meters below ground or 9.6 meters above ground for residential units.
Is documentation in English allowed for Danish building projects?
Yes, according to BR18 § 507, documentation of fire safety conditions can be prepared in either Danish or English.
What is a common escape route (fælles flugtvej)?
A common escape route is an exit path designed to serve multiple building sections simultaneously, requiring fire safety measures that satisfy all connected sections.